The Heater Interlock
Part of the Analog and Sequences section of Coddy's PLC Programming journey. Lesson 11 of 17.
The batch should leave warm, so the heater runs while it mixes and keeps running while it drains. But a heater must never run without liquid over it.
An interlock is a condition that blocks an output, whatever else asks for it. Low is TRUE only while liquid covers the heater, so a Low contact in series is the heater's interlock. As the tank drains below 20 %, the heater turns off, even though step 3 still asks for heat.
Challenge
Medium- turn
Heateron in steps 2 and 3 - interlock it with
Low, so it turns off as the level drains below 20 %
Try it yourself
{"v":1,"lang":"ld","tags":[{"name":"Step","type":"INT"},{"name":"T1","type":"TON"}],"rungs":[{"els":[{"t":"cmp","op":"EQ","a":"Step","b":0},{"t":"no","tag":"Start"},{"t":"move","src":1,"dst":"Step"}]},{"els":[{"t":"cmp","op":"EQ","a":"Step","b":1},{"t":"no","tag":"High"},{"t":"move","src":2,"dst":"Step"}]},{"els":[{"t":"cmp","op":"EQ","a":"Step","b":2},{"t":"TON","inst":"T1","pt":"T#5s"},{"t":"move","src":3,"dst":"Step"}]},{"els":[{"t":"cmp","op":"EQ","a":"Step","b":3},{"t":"cmp","op":"EQ","a":"Level","b":0},{"t":"move","src":0,"dst":"Step"}]},{"els":[{"t":"nc","tag":"Stop"},{"t":"move","src":0,"dst":"Step"}]},{"els":[{"t":"cmp","op":"EQ","a":"Step","b":1},{"t":"coil","tag":"Fill"}]},{"els":[{"t":"cmp","op":"EQ","a":"Step","b":2},{"t":"coil","tag":"Mixer"}]},{"els":[{"t":"cmp","op":"EQ","a":"Step","b":3},{"t":"coil","tag":"Drain"}]}]}This lesson includes a short quiz. Start the lesson to answer it and track your progress.