Part of the Timers section of Coddy's PLC Programming journey. Lesson 3 of 18.

Big machines often start a moment after the button: time for a warning, or for another machine to get going first. The button cannot hold the timer, because Start is pressed only for a moment.

So the seal-in latches a memory bit, Run, and the timer runs from it. The motor starts when the timer is done.

Stop breaks the seal-in, Run turns off, the timer resets and the motor stops at once. A Stop during the delay cancels the start.

challenge icon

Challenge

Easy

Make Start run the motor 2 s after it is pressed:

  • change the seal-in so it latches a memory bit Run
  • add a rung: Run, a TON with T#2s, then the Motor coil

Stop must still stop the motor at once.

Try it yourself