A Latched Fault

Part of the Latches, Edges and Interlocks section of Coddy's PLC Programming journey. Lesson 14 of 20.

A fault lamp that goes out as soon as the overload relay is reset hides what happened. Someone who arrives later sees nothing. So machines latch faults: the lamp stays lit until an operator acknowledges it.

A trip sets FaultLamp and a press of Stop resets it. Both contacts are normally closed: both inputs are wired NC, and each rung needs power while its input reads FALSE.

Put the set rung last, so Stop cannot clear a fault that is still there. For a motor Stop must win; for a fault the fault must win.

challenge icon

Challenge

Medium

Add two rungs: a press of Stop resets FaultLamp, and a tripped Overload sets it, on the rung below. Switch the overload to Trip, then back to OK: the lamp stays lit until Stop.

Try it yourself

{"v":1,"lang":"ld","tags":[],"rungs":[{"els":[{"t":"par","branches":[[{"t":"no","tag":"Fwd"},{"t":"nc","tag":"Rev"}],[{"t":"no","tag":"MotorFwd"}]]},{"t":"no","tag":"Stop"},{"t":"no","tag":"Overload"},{"t":"nc","tag":"MotorRev"},{"t":"coil","tag":"MotorFwd"}]},{"els":[{"t":"par","branches":[[{"t":"no","tag":"Rev"},{"t":"nc","tag":"Fwd"}],[{"t":"no","tag":"MotorRev"}]]},{"t":"no","tag":"Stop"},{"t":"no","tag":"Overload"},{"t":"nc","tag":"MotorFwd"},{"t":"coil","tag":"MotorRev"}]},{"els":[]}]}