Part of the Latches, Edges and Interlocks section of Coddy's PLC Programming journey. Lesson 3 of 20.

Set and reset coils can run a motor without a seal-in: Start sets Motor, Stop resets it.

Careful with Stop. It is wired NC, so it reads FALSE while pressed. The reset rung must have power while Stop is pressed, so it needs a contact that passes power while the tag is FALSE: a normally closed contact.

In the seal-in, Stop was a normally open contact, because there it had to pass power while nobody pressed it. So always ask: should this contact pass power while the button is pressed, or while it is not?

On some PLCs a set bit survives a power cut, so the motor starts again when power returns. A seal-in does not, which is why many sites prefer it for motors.

challenge icon

Challenge

Easy

Write two rungs: Start sets Motor, and Stop resets it. The motor keeps running after Start is released.