The Interlock

Part of the Latches, Edges and Interlocks section of Coddy's PLC Programming journey. Lesson 12 of 20.

If both contactors close together, two phases are connected straight to each other: a short circuit. The breaker trips and nothing runs until it is reset. Try it with the program as it is: start forward, then press Rev.

The fix is an interlock. Each direction's rung gets a normally closed contact of the other direction's output, so while the motor runs forward the reverse rung cannot pass power.

To change direction the operator presses Stop first. Real panels also wire the interlock in hardware, with a contact on each contactor, in case the program is wrong or a contactor sticks closed.

challenge icon

Challenge

Medium

Add an interlock to both rungs: a normally closed MotorRev contact on the forward rung, and a normally closed MotorFwd contact on the reverse rung.

Try it yourself

{"v":1,"lang":"ld","tags":[],"rungs":[{"els":[{"t":"par","branches":[[{"t":"no","tag":"Fwd"}],[{"t":"no","tag":"MotorFwd"}]]},{"t":"no","tag":"Stop"},{"t":"no","tag":"Overload"},{"t":"coil","tag":"MotorFwd"}]},{"els":[{"t":"par","branches":[[{"t":"no","tag":"Rev"}],[{"t":"no","tag":"MotorRev"}]]},{"t":"no","tag":"Stop"},{"t":"no","tag":"Overload"},{"t":"coil","tag":"MotorRev"}]}]}