Someone must be able to stop the door anywhere. Like every Stop button, the door's Stop is wired NC: TRUE at rest, FALSE while pressed, so a broken wire stops the door too.

It goes in series on both rungs, as a normally open contact, so it passes power while nobody presses it.

A press breaks both seal-ins, and the door stays where it is until Open or Close.

challenge icon

Challenge

Easy

Add Stop to both rungs, so a press stops the door wherever it is.

Try it yourself

{"v":1,"lang":"ld","tags":[],"rungs":[{"els":[{"t":"par","branches":[[{"t":"no","tag":"Open"}],[{"t":"no","tag":"MotorUp"}]]},{"t":"nc","tag":"UpLimit"},{"t":"nc","tag":"MotorDown"},{"t":"coil","tag":"MotorUp"}]},{"els":[{"t":"par","branches":[[{"t":"no","tag":"Close"}],[{"t":"no","tag":"MotorDown"}]]},{"t":"nc","tag":"DownLimit"},{"t":"nc","tag":"MotorUp"},{"t":"coil","tag":"MotorDown"}]}]}